xraytools.

X-ray Tube Spectrum

What actually comes out of an X-ray tube — a continuous Bremsstrahlung spectrum with the anode’s characteristic lines standing on it. The continuum stops dead at λmin = hc/eU, which depends on the accelerating voltage and on nothing else at all.

You supply
An anode and a tube voltage in kV. A current in mA as well, if you want the power and the heat load.
Reading it
The limit is exacthc/e is arithmetic, not a measurement. The continuum’s shape is Kramers’ idealisation and a real tube peaks nearer 1.5λmin. The excitation figure is a lower bound, not the threshold: this site ships no absorption-edge energies, so what it can say is that the edge lies above Kβ.

Worked examples: a copper tube at 40 kV · molybdenum at 50 kV · silver at 20 kV — no lines · the same tube at 50 kV

Input

kV
mA

Blank means 40 kV and 30 mA. The current changes how much comes out and nothing about which wavelengths do.

The short-wavelength limit does not depend on the anode. Change it and the continuum stays exactly where it is; only the sharp lines move.

The spectrum

0.000.240.480.720.96wavelength / Åintensity per unit wavelength (Kramers, arbitrary scale)λmin = 0.2480 Åmin

Mo anode (Z = 42) at 50 kV. The continuum starts at 0.2480 Å and peaks at 0.4959 Å.

The curve is Kramers’ law (1923), I(λ) ∝ (λ/λmin − 1)/λ2, which is the spectrum of an idealised target: every electron stops in one step, and nothing absorbs the photons on the way out. Its maximum falls at exactly 2λmin — substitute u = λ/λmin and the derivative of (u − 1)/u2 vanishes at u = 2, whatever the voltage. A real tube peaks nearer 1.5λmin, because the anode reabsorbs its own soft radiation and the beryllium window absorbs more of it — both of which eat the long side of the curve and neither of which is in the formula. The short side is not affected: λmin itself is exact.

The picture draws one Kα line where the table lists two. Kα1 and Kα2 are 0.00429 Å apart, against a frame about 1.0 Å wide — about one part in 225, so at the scale of a whole tube spectrum they are one line and no amount of redrawing separates them. The position marked is the weighted mean, which is what a detector that cannot resolve them measures. You see the doublet in a diffraction pattern instead, at high angle, where Bragg’s law spreads the two apart in 2θ.

The characteristic lines are drawn where they fall, not how tall they are. Their heights relative to each other are meaningful — Kα1 is twice Kα2, which this site recovers from its own wavelength constants rather than being told — but their height relative to the continuum is not computed here: it depends on how far the voltage overshoots the edge, on the fluorescence yield and on the target’s self-absorption, and this site holds none of those. In a real diffraction experiment Kα towers over the background by a factor of some hundreds, which is the only reason the method works at all.

The characteristic lines, and whether this voltage reaches them

A K line appears only once the beam can knock a 1s electron out of the anode altogether, which takes the K absorption edge energy — and this site ships no edge energies and predicts none. What it can give is a bound that needs no extra data: the edge lies above Kβ, because Kβ only has to reach the M shell while the edge has to reach the continuum. So 19.609 kV is a voltage the tube must exceed — a necessary condition, not a sufficient one. The true figure for Mo is a little higher; for the lighter anodes the gap is under a per cent, and it widens with atomic number as the M shell pulls away from the continuum.

Line λ / Å Energy / keV Height drawn At 50 kV
0.63229 19.609 0.30 nominal present
1 0.70930 17.480 1.00 present
2 0.71359 17.375 0.50 present

All three lines switch on together, at the same voltage: they all begin with a hole in the K shell, so what has to be paid for is the ionisation and not the transition. The Kα1 : Kα2 height of 2.00 : 1 is not typed in anywhere — it is solved back out of this site’s own three wavelength constants for Mo, whose Kα value is the weighted mean of the other two.

How this is calculated

An electron accelerated through U arrives at the anode with kinetic energy eU. The most energetic photon it can produce is the one that takes all of that energy in a single stop:

eU=hνmax=hcλmin

The reader typed a voltage and the formula wants an energy, and here they are the same numeral: one electron through 50 kV picks up 50 keV, because that is what an electronvolt is defined to be. So with hc/e in the units this site works in — 12.398420 keV Å, which is exact, since h, c and e are all defined constants in the SI:

λmin=hceU=12.398420keV Å50keV=0.2480

Nothing in that line mentions the anode. The limit is a property of the voltage alone, which is why every tube on this site has the same short-wavelength limit at the same setting — and why the characteristic lines, which are a property of the anode alone, are the only part of the spectrum that moves when you change it.

Power, and where nearly all of it goes

Kramers also estimates what fraction of the beam power leaves as X-rays: η ≈ 1.1 × 10−9 Z U, with U in volts. For this tube that is 0.231%, so of 1,500 W going in, about 3.5 W comes out as X-rays and the rest — 1,497 W — is heat the anode has to lose. The textbook figure of “1% X-rays, 99% heat” is a tungsten tube at 100 kV; a crystallography tube runs a light anode at a third of the voltage, so it is nearer a tenth of a per cent. That is why the anode is water-cooled, why a rotating anode exists at all, and why a microfocus source can manage on 30 W.

Beam power U × i 1,500.0 W
Out as X-rays (Kramers) 3.47 W — 0.231%
Left as heat 1,496.5 W
Total intensity IZ U2 i 1.563 × the same anode at 40 kV, 30 mA

That last row is a ratio, not a measurement: the law is written with a proportionality and carries no constant, so it compares two settings of the same tube and says nothing about photons per second. Doubling the current doubles it; doubling the voltage quadruples it, and shifts the whole continuum to shorter wavelengths at the same time.

What was used

hc/e 12.398420 keV Å — exact, not measured: h, c and e have all been defined constants in the SI since 2019
λmin 0.24797 Å
Continuum maximum 0.49594 Å — exactly 2λmin, for any voltage
Lower bound on the K threshold 19.609 keV — the Kβ photon energy, which the absorption edge exceeds
Plotted out to 0.963 Å

Try it

a copper tube at 40 kV · molybdenum at 50 kV · silver at 20 kV — no lines · the same tube at 50 kV